Power plant controls
Introduction
While it is
theoretically possible to operate a boiler with manual control the operator
must maintain a tedious, constant which for disturbances and variations of
parameters. Time is needed for the boiler to respond to a correction and this
lead to over correction with further upset to the boiler. An automatic
controller once properly tuned will make the proper adjustment quickly to minimize
upsets and will control the system more accurately and reliably. Instrumentation systems are
provided for the boiler to achieve the following:
1. To
measure the actual values of different parameters for which the boiler is
designed.
2. Safe
working range of the different parameters is maintained.
3. To
monitor one or more variables at a time and provide input for automatic
control.
4. In case
of operator failure to take remedial action for an upset condition, it protects
the boiler by alarms and trippings.
5. To
provide data on operating conditions before failure of the equipment for
analysing the failure.
Special
care is required to be taken while selecting the instrumentation for the
boiler. Simple auto control loops, avoiding duplication of instruments and
selecting proven instruments with the correct operating range forms the basis
of the reliable instrumentation. There are many instruments and control loops
that are provided for a boiler. Based on the feed backs collected from various
operating sugar plants a few of the important protection and controls which are
essential are listed below:
Drum level high & low
protection
The water
level in the steam drum has to be maintained within the desired limits. The reduction
of drum level below the low level mark will cause tube failures and level above
the high level mark will cause water carry over to the turbine. Hence it is
essential to have reliable direct level gauge on both ends of the drum. A low
level trip to shut down the boiler in case the water level falls below the allowable
limit and a very high level trip/ alarm has been suggested for all boilers. At
present it is noticed that these contacts for the indication / alarm has been
taken from the drum level controller, which is not preferred. Due to many
reasons if the controller is isolated during operation of the boiler the
protection is not available. It is always recommended that a separate level
switch be provided for eater level low and high alarm and trip.
Furnace temperature probe
The new
series of the boilers require controlled start up and loading programs. Most of
the manufacturers provide a start up curve which generally gives the rate of
pressure increase in the boiler to be followed. During start up of the boiler
adequate steam flow is not established through the super heater. Hence high
rate of heat input if provided to the boiler furnace will result in high
furnace outlet temperature of the flue gas causing overheating and tube
failure. It is advisable to control the rate of heat input into the boiler and
maintain the flue gas temperature leaving the furnace at around 540o C. A
furnace temperature probe is a high temperature thermocouple surrounded by a
jacket of water. Cooling water can be circulating through the jacket to protect
the thermocouple from overheating. Once adequate steam flow is established
through the super heater there would not be any limitation on the rate of fuel
firing. Temperature probes without cooling water are also available, it
requires the thermocouple to be withdrawn when the temperature of the flue
gases exceeds 540o C. This thermocouple has an advance and retract mechanism
similar to that of a long retractable soot blower. A protection to retract the
furnace probe with alarm when the flue gas outlet temperature from furnace
exceeds the allowable value, must be provided. This temperature probe is
recommended to be installed to avoid, operator failure and ensure protection
for super-heater during start-up and shut down. Fig 1 indicates a typical water
cooled thermocouple without advance and retract mechanism. As a temporary
measure mineral insulated, monel sheathed, 6 mm diameter thermocouple with
sleeve capable of measuring maximum of 950o C temperature can be fixed in the
furnace outlet zone to monitor the flue gas temperature.
Steam purity
Purity of
steam indicates the extent of carryover of salts from boiler water with the steam.
Sodium salts in boiler water gets carried over due to various reasons with the steam
and deposits in the super heater inner surfaces and turbine b lades causing
reduction of equipment life and availability of the boiler. Steam drums are
provided with drier box arrangement to avoid carry over. Constant maintenance
and inspection of these internals in an essential activity of the boiler operation.
The purity of steam should be monitored periodically to improve the
availability of the boiler. The method of obtaining the steam sample plays a
vital role in the measurement of its purity. It is recommended that the
sampling lines should be of stainless steel and the cooling coils in the sample
coolers should be located close to the sampling point to minimize settling and
contamination from the sample line. Sodium tracer technique permits measuring
dissolved solids in steam to as low as 0.001 ppm. The operation of a flame
photometer is illustrated in Figure 2. The condensed steam sample is aspirated
through a small tube in the burner into the oxygen -hydrogen flame. The flame,
at about 1700o C, vaporizes the water and excites the sodium atoms, which emits
a characteristic yellow light having a definite wavelength. The intensity of
the emitted yellow light is a measure of the sodium in the sample. The intensity
of the light is measured with a spectrophotometer equipped with a
photomultiplier attachment.
The light
from the flame is focused by the condensing mirror and is directed to the diagonal
entrance mirror. The entrance mirror deflects the light through the entrance
slit and into the monochromatic to the plane mirror. Light striking the plane
mirror is reflected to the fiery prism where it is dispersed into its component
wavelengths. The desired light wavelength is obtained by rotating a wavelength selector
which adjusts the position of the prism. The selected wavelength is directed
back to the plane mirror where it is reflected through the adjustable exit slit
and lens. The light impinges on the photomultiplier tube, causing a current
gain which registers on the meter. The amount of sodium in the sample is
obtained by comparing the emission from the water sample to emissions obtained
from solutions of known concentration.
Control loops
For the
generation of steam to be continuous, it follows that the control also should
be continuous and the needed adjustments for air flow, fuel flow, water flow,
etc., shou ld be adjusted simultaneously. Manual control of these variables
depends much on the ability of the operator to judge and correct the parameters
without too many trial and error operations. Automatic boiler control is the
best course of maintaining a steady output from the boiler. Advancements in
electronics have made electronic control systems more favorable when compared
to pneumatic and other outdated systems. In case of cogeneration plants the
complex interdependent of the turbo generator on the boiler to maintain a
constant output when paralleled with state power grid would justify introduction
of distributed data control system.
A few
advantages of the electronic system can be listed as below:
a. High
speed of signal transmission and low time lag.
b.
Possibility for amplification of signal
c. Easily
adaptable to complex and integrated control.
d. Greater
accuracy due to fast response and feedback from more number of interdependent
variables.
Electronic
control system with final operating element either electric or pneumatic system
is preferred as this results in high speed and high motive force. The following
are some of the vital control loops that are recommended for the modern high
pressure sugar plant boilers.
Feed water control / drum
level control
Maintaining
drum level at the normal recommended operating level is very important. Too low
a water level can cause starvation in boiler tubes and lead to failures. Too
high a level will lead to carry over of boiler water and reduce the s team
purity.
Three element system for drum
level control:
Feed water
flow to the drum should be continuous, failure of flow even for a brief period can
cause serious and hazardous effect on the plant and operating personnel. Many
of the modern boilers today operate at steam temperatures near the maximum permissible
metal temperatures and temperatures fluctuation as a result of poor feed water
control can cause damage to the boiler tubes. In the design of the boiler
advantage is taken of the high level of performance achieved by high steam
release to water ratio. This high ratio calls for a highly reliable water level
control. The three elements employed are drum level, steam flow and feed water
flow. In this system (fig 3) the basic control is from the relation of the
steam flow to feed water flow. In closed system, under normal steady conditions,
with the drum level at the correct value, the ratio of steam flow to feed flow
will be 1:1. Any change in this condition will result in a control signal being
applied to the feed water control valve. The signal from water level also will
affect the readjustment of the feed water valve to trim the level back to its
desired value, once stability is achieved. Water flow measurement signal enters
the control system to position the regulating valve in the feed water line so
that the water input equals the steam output from the boiler. Therefore any
variations in feed water pressure ahead of the regulating valve, causing change
in water flow will at once be detected by the flow meter and the regulating
valve will react.
Furnace Draft Control System
In all the
combustion control system, irrespective of the type, an independent control
loop is provided to maintain a constant negative draft inside the combustion c
hamber. Any variation from the set value is detected by the controller, and the
resultant output signal directly goes to regulate the position of the I.D fan
damper.
Steam Temperature Control
System
With the
spray at temperate or desuperheater method, fine jets of water on steam condensate
is sprayed through nozzles into the steam in its passage between the first and second
stages of super heaters. In order to achieve this, the temperature of steam is measured
and any variation from a desired value is detected by a controller. The latter then
sends out a signal to the regulating valve in the injection line. The system as
shown in Fig.5 is suitable for sugar plant boilers where the mass of the super
heater and hence, thermal inertia time is small. This greatly minimizes the
time lag in the heat transfer.
Combustion Control System
The main
object of automatic boiler combustion control is to regulate automatically, the
heat input to a boiler in terms of fuel and air supplied in relation to eat
output or steam demand. This should be implemented as efficiently as possible
in terms of combustion quality and furnace stability. Combustion air supplies
are to be adjusted with change in boiler loads. Steam pressure is taken as the
indication for boiler load as the steam pressure is taken as the indication for
boiler load as the steam pressure decreases in increasing load and vice versa.
Hence variations in steam pressure is detected and the supply of the fuel and
air adjusted accordingly. (Refer Fig.6)
The
successful operation of the combustion control system depends upon the
capability to vary the fuel supply to the furnace based on the signals from the
control system.To achieve this a system of bagasse storage and retrieval
facility with about half an hour holding capacity, should be provided before
the bagasse system.
Essential interlocks for
Boiler
For safe
operation of boiler and auxiliaries even in the event of a failure of the
control system it is necessary to provide certain interlocks and trips in th e
control system.
Boiler trip protection
The sugar
plant boiler should be provided with trip facility which will shut down the systems
when it receives a trip command for the following conditions or if boiler trip push
button provided in the panel is depressed.
a. FD fan
trip / shut down
b. ID fan
trip / shut down
c.
Cogeneration turbine trip
d. Drum
level low / high trip
Some of the
essential interlocks recommended for start up of boiler auxiliaries are:
a. Start ID
fan when FD fan and PA fan are off.
b. Start FD
fan only if ID fan is on.
c. Start PA
fan only if both FD and ID fans are on
d. Start
bagasse feeder only if PA fan is on
e. ID fan
is of all fans shall trip.
f. Trip bagasse
feeders when PA fan is tripped.
Comments
Post a Comment